Wire size for 200 amps at 25 feet
The smallest wire that carries 200 amps safely, then checked so no more than 3% of the voltage is lost over 25 feet at 240 volts.
NM-B house cable (Romex)
Not NM-B
Over 55 amps or this far, run wires in conduit or SER cable.
Copper wires in conduit (THHN)
3/0 AWG
0.32% voltage drop
Aluminum (SER or XHHW)
250 kcmil
0.35% voltage drop
For a whole-house service only: NEC 310.12 lets a dwelling's main service or feeder run at 83% of its rating, so 200 A can use 2/0 AWG copper or 4/0 AWG aluminum. That does not apply to a subpanel feeder or a single circuit.
Every size at 25 feet and 200 amps
| Size | Carries, NM-B (60°C) | Carries, conduit (75°C) | Drop, copper | Drop, aluminum |
|---|---|---|---|---|
| 14 AWG | 15 A | 15 A | 12.8% | - |
| 12 AWG | 20 A | 20 A | 8.04% | 13.3% |
| 10 AWG | 30 A | 30 A | 5.04% | 8.33% |
| 8 AWG | 40 A | 50 A | 3.18% | 5.25% |
| 6 AWG | 55 A | 65 A | 2.05% | 3.37% |
| 4 AWG | 70 A | 85 A | 1.28% | 2.12% |
| 3 AWG | 85 A | 100 A | 1.02% | 1.68% |
| 2 AWG | 95 A | 115 A | 0.81% | 1.33% |
| 1 AWG | 110 A | 130 A | 0.64% | 1.05% |
| 1/0 AWG | 125 A | 150 A | 0.51% | 0.84% |
| 2/0 AWG | 145 A | 175 A | 0.40% | 0.66% |
| 3/0 AWG | 165 A | 200 A | 0.32% | 0.53% |
| 4/0 AWG | 195 A | 230 A | 0.25% | 0.42% |
| 250 kcmil | 215 A | 255 A | 0.21% | 0.35% |
| 300 kcmil | 240 A | 285 A | 0.18% | 0.29% |
| 350 kcmil | 260 A | 310 A | 0.15% | 0.25% |
How the size is picked
- Amps first. The wire has to carry the breaker's amps: NEC Table 310.16, with NM-B house cable held to the 60°C column and wires in conduit to the 75°C column. Small wires are capped at 15 A for 14 AWG, 20 A for 12 AWG and 30 A for 10 AWG copper.
- Then distance. Long runs lose voltage. The size goes up until no more than 3% is lost, the figure the NEC recommends for a branch circuit, using the wire resistances in NEC Chapter 9, Table 8.
- Distance is one way. Measure from the panel to the load; the math counts the trip out and back.
Motors, EV chargers and anything that runs for three hours or more are sized at 125% of their load. Local codes can be stricter; your inspector has the last word.