Outlets and GFCI

Count the cables in the box: one cable means the end of the run, two means power passes through to more outlets. A 3-wire cable from a switch means a half-switched outlet.

Questions people ask at the box

Which side of an outlet is hot?

The brass screws are hot (black wire) and feed the shorter slot. The silver screws are neutral (white wire) and feed the taller slot. The green screw is ground.

Can I put a 15 amp outlet on a 20 amp circuit?

Yes, as long as the circuit has more than one outlet (NEC 210.21(B)(3)). A single outlet alone on a 20 amp circuit must be a 20 amp outlet. The wire on a 20 amp circuit must be 12 AWG either way.

What do LINE and LOAD mean on a GFCI?

LINE takes the power coming in from the panel. LOAD feeds the outlets after it, and protects them too. With only one cable in the box, use LINE and leave the LOAD screws taped.

Can I put a GFCI where there is no ground wire?

Yes. The code allows a GFCI to replace an ungrounded two-prong outlet (NEC 406.4(D)(2)) as long as it is labeled "No Equipment Ground". It protects people from shock even without a ground.

Screws or the push-in holes on the back?

Use the side screws. Push-in holes on most outlets only take 14 AWG wire and loosen over time; screws hold firmly.