Wire size for 150 amps at 250 feet
The smallest wire that carries 150 amps safely, then checked so no more than 3% of the voltage is lost over 250 feet at 240 volts.
NM-B house cable (Romex)
Not NM-B
Over 55 amps or this far, run wires in conduit or SER cable.
Copper wires in conduit (THHN)
3/0 AWG
1/0 AWG carries the amps; one size up keeps the drop to 2.39%
Aluminum (SER or XHHW)
250 kcmil
3/0 AWG carries the amps; larger keeps the drop to 2.65%
For a whole-house service only: NEC 310.12 lets a dwelling's main service or feeder run at 83% of its rating, so 150 A can use 1 AWG copper or 2/0 AWG aluminum. That does not apply to a subpanel feeder or a single circuit.
Every size at 250 feet and 150 amps
| Size | Carries, NM-B (60°C) | Carries, conduit (75°C) | Drop, copper | Drop, aluminum |
|---|---|---|---|---|
| 14 AWG | 15 A | 15 A | 95.9% | - |
| 12 AWG | 20 A | 20 A | 60.3% | 99.4% |
| 10 AWG | 30 A | 30 A | 37.8% | 62.5% |
| 8 AWG | 40 A | 50 A | 23.9% | 39.4% |
| 6 AWG | 55 A | 65 A | 15.3% | 25.3% |
| 4 AWG | 70 A | 85 A | 9.63% | 15.9% |
| 3 AWG | 85 A | 100 A | 7.66% | 12.6% |
| 2 AWG | 95 A | 115 A | 6.06% | 9.97% |
| 1 AWG | 110 A | 130 A | 4.81% | 7.91% |
| 1/0 AWG | 125 A | 150 A | 3.81% | 6.28% |
| 2/0 AWG | 145 A | 175 A | 3.02% | 4.97% |
| 3/0 AWG | 165 A | 200 A | 2.39% | 3.94% |
| 4/0 AWG | 195 A | 230 A | 1.90% | 3.13% |
| 250 kcmil | 215 A | 255 A | 1.61% | 2.65% |
| 300 kcmil | 240 A | 285 A | 1.34% | 2.21% |
| 350 kcmil | 260 A | 310 A | 1.15% | 1.89% |
How the size is picked
- Amps first. The wire has to carry the breaker's amps: NEC Table 310.16, with NM-B house cable held to the 60°C column and wires in conduit to the 75°C column. Small wires are capped at 15 A for 14 AWG, 20 A for 12 AWG and 30 A for 10 AWG copper.
- Then distance. Long runs lose voltage. The size goes up until no more than 3% is lost, the figure the NEC recommends for a branch circuit, using the wire resistances in NEC Chapter 9, Table 8.
- Distance is one way. Measure from the panel to the load; the math counts the trip out and back.
Motors, EV chargers and anything that runs for three hours or more are sized at 125% of their load. Local codes can be stricter; your inspector has the last word.