Wire size for 100 amps at 250 feet

The smallest wire that carries 100 amps safely, then checked so no more than 3% of the voltage is lost over 250 feet at 240 volts.

Volts

NM-B house cable (Romex)

Not NM-B

Over 55 amps or this far, run wires in conduit or SER cable.

Copper wires in conduit (THHN)

1/0 AWG

3 AWG carries the amps; one size up keeps the drop to 2.54%

Aluminum (SER or XHHW)

3/0 AWG

1 AWG carries the amps; larger keeps the drop to 2.63%

For a whole-house service only: NEC 310.12 lets a dwelling's main service or feeder run at 83% of its rating, so 100 A can use 4 AWG copper or 2 AWG aluminum. That does not apply to a subpanel feeder or a single circuit.

Every size at 250 feet and 100 amps

SizeCarries, NM-B (60°C)Carries, conduit (75°C)Drop, copperDrop, aluminum
14 AWG15 A15 A64.0%-
12 AWG20 A20 A40.2%66.3%
10 AWG30 A30 A25.2%41.7%
8 AWG40 A50 A15.9%26.3%
6 AWG55 A65 A10.2%16.8%
4 AWG70 A85 A6.42%10.6%
3 AWG85 A100 A5.10%8.40%
2 AWG95 A115 A4.04%6.65%
1 AWG110 A130 A3.21%5.27%
1/0 AWG125 A150 A2.54%4.19%
2/0 AWG145 A175 A2.01%3.31%
3/0 AWG165 A200 A1.60%2.63%
4/0 AWG195 A230 A1.27%2.08%
250 kcmil215 A255 A1.07%1.76%
300 kcmil240 A285 A0.89%1.47%
350 kcmil260 A310 A0.76%1.26%

How the size is picked

  1. Amps first. The wire has to carry the breaker's amps: NEC Table 310.16, with NM-B house cable held to the 60°C column and wires in conduit to the 75°C column. Small wires are capped at 15 A for 14 AWG, 20 A for 12 AWG and 30 A for 10 AWG copper.
  2. Then distance. Long runs lose voltage. The size goes up until no more than 3% is lost, the figure the NEC recommends for a branch circuit, using the wire resistances in NEC Chapter 9, Table 8.
  3. Distance is one way. Measure from the panel to the load; the math counts the trip out and back.

Motors, EV chargers and anything that runs for three hours or more are sized at 125% of their load. Local codes can be stricter; your inspector has the last word.