Wire size for 90 amps at 150 feet

The smallest wire that carries 90 amps safely, then checked so no more than 3% of the voltage is lost over 150 feet at 240 volts.

Volts

NM-B house cable (Romex)

Not NM-B

Over 55 amps or this far, run wires in conduit or SER cable.

Copper wires in conduit (THHN)

3 AWG

2.76% voltage drop

Aluminum (SER or XHHW)

1 AWG

2 AWG carries the amps; larger keeps the drop to 2.85%

Every size at 150 feet and 90 amps

SizeCarries, NM-B (60°C)Carries, conduit (75°C)Drop, copperDrop, aluminum
14 AWG15 A15 A34.5%-
12 AWG20 A20 A21.7%35.8%
10 AWG30 A30 A13.6%22.5%
8 AWG40 A50 A8.60%14.2%
6 AWG55 A65 A5.52%9.09%
4 AWG70 A85 A3.46%5.71%
3 AWG85 A100 A2.76%4.53%
2 AWG95 A115 A2.18%3.59%
1 AWG110 A130 A1.73%2.85%
1/0 AWG125 A150 A1.37%2.26%
2/0 AWG145 A175 A1.09%1.79%
3/0 AWG165 A200 A0.86%1.42%
4/0 AWG195 A230 A0.68%1.13%
250 kcmil215 A255 A0.58%0.95%
300 kcmil240 A285 A0.48%0.80%
350 kcmil260 A310 A0.41%0.68%

How the size is picked

  1. Amps first. The wire has to carry the breaker's amps: NEC Table 310.16, with NM-B house cable held to the 60°C column and wires in conduit to the 75°C column. Small wires are capped at 15 A for 14 AWG, 20 A for 12 AWG and 30 A for 10 AWG copper.
  2. Then distance. Long runs lose voltage. The size goes up until no more than 3% is lost, the figure the NEC recommends for a branch circuit, using the wire resistances in NEC Chapter 9, Table 8.
  3. Distance is one way. Measure from the panel to the load; the math counts the trip out and back.

Motors, EV chargers and anything that runs for three hours or more are sized at 125% of their load. Local codes can be stricter; your inspector has the last word.