Wire size for 60 amps at 50 feet

The smallest wire that carries 60 amps safely, then checked so no more than 3% of the voltage is lost over 50 feet at 240 volts.

Volts

NM-B house cable (Romex)

Not NM-B

Over 55 amps or this far, run wires in conduit or SER cable.

Copper wires in conduit (THHN)

6 AWG

1.23% voltage drop

Aluminum (SER or XHHW)

4 AWG

1.27% voltage drop

Every size at 50 feet and 60 amps

SizeCarries, NM-B (60°C)Carries, conduit (75°C)Drop, copperDrop, aluminum
14 AWG15 A15 A7.68%-
12 AWG20 A20 A4.83%7.95%
10 AWG30 A30 A3.02%5.00%
8 AWG40 A50 A1.91%3.15%
6 AWG55 A65 A1.23%2.02%
4 AWG70 A85 A0.77%1.27%
3 AWG85 A100 A0.61%1.01%
2 AWG95 A115 A0.49%0.80%
1 AWG110 A130 A0.39%0.63%
1/0 AWG125 A150 A0.30%0.50%
2/0 AWG145 A175 A0.24%0.40%
3/0 AWG165 A200 A0.19%0.32%
4/0 AWG195 A230 A0.15%0.25%
250 kcmil215 A255 A0.13%0.21%
300 kcmil240 A285 A0.11%0.18%
350 kcmil260 A310 A0.09%0.15%

How the size is picked

  1. Amps first. The wire has to carry the breaker's amps: NEC Table 310.16, with NM-B house cable held to the 60°C column and wires in conduit to the 75°C column. Small wires are capped at 15 A for 14 AWG, 20 A for 12 AWG and 30 A for 10 AWG copper.
  2. Then distance. Long runs lose voltage. The size goes up until no more than 3% is lost, the figure the NEC recommends for a branch circuit, using the wire resistances in NEC Chapter 9, Table 8.
  3. Distance is one way. Measure from the panel to the load; the math counts the trip out and back.

Motors, EV chargers and anything that runs for three hours or more are sized at 125% of their load. Local codes can be stricter; your inspector has the last word.